Reference Manual
00809-0100-4697, Rev GA
Appendix D: Function Blocks
November 2014
Function Blocks
CHANNEL
If the device supports more than one measurement, verify that the selected channel
contains the appropriate measurement or derived value. Refer to Table D-4 on page 106 for
a listing of available channels on the 848T.
L_TYPE
Select Direct when the measurement is already in the desired engineering units for the
block output. Select Indirect when converting the measured variable into another, for
example, pressure into level or flow into energy. Select Indirect Square Root when the block
I/O parameter value represents a flow measurement made using differential pressure, and
when square root extraction is not performed by the transducer.
SCALING
XD_SCALE provides the range and units of the measurement and OUT_SCALE provides the
range and engineering units of the output.
D.2.2 MAI block troubleshooting
Symptom Possible causes Corrective action
Mode will not leave
OOS
Target mode not set Set target mode to something other than OOS.
Configuration error BLOCK_ERR will show the configuration error bit set. The following are
parameters that must be set before the block is allowed out of OOS:
•Initial value is 1.
•XD_SCALE
.UNITS_INDEX must match the units in all the corresponding
sensor transducer blocks.
• L_TYPE must be set to Direct, Indirect, or Indirect Square Root and cannot be
left at initial value of 0.
Resource block The actual mode of the Resource block is OOS. See Resource Block
Diagnostics for corrective action.
Schedule Block is not scheduled and therefore cannot execute to go to Target
Mode. Typically, BLOCK_ERR will show “Power-Up” for all blocks that are
not scheduled. Schedule the block to execute.
Process and/or block
alarms will not work.
Features FEATURES_SEL does not have Alerts enabled. Enable the Alerts bit.
Notification LIM_NOTIFY is not high enough. Set equal to MAX_NOTIFY.
Status Options STATUS_OPTS has Propagate Fault Forward bit set. This should be
cleared to cause an alarm to occur.
Value of output does
not make sense
Linearization Type L_TYPE must be set to Direct, Indirect, or Indirect Square Root and
cannot be left at initial value of 0.
Scaling Scaling parameters are set incorrectly:
• XD_SCALE.EU0 and EU100 should match that of the corresponding sensor
transducer block.
•OUT_SCALE
.EU0 and EU100 are not set properly.
• Both STBs in an ASIC must be set to auto. Best in 1, 2, 7, 8, ASICs in Auto for
thermocouples