99
Reference Manual
00809-0100-4697, Rev GA
Appendix D: Function Blocks
November 2014
Function Blocks
18 PV_FTIME Seconds
The time constant of the first-order PV filter. It is the
time required for a 63% change in the PV or OUT
value.
19 FIELD_VAL Percent
The value and status from the transducer block or
from the simulated input when simulation is enabled.
20 UPDATE_EVT None
This alert is generated by any change to the static
data.
21 BLOCK_ALM None
The block alarm is used for all configuration,
hardware, connection failure or system problems in
the block. The cause of the alert is entered in the
subcode field. The first alert to become active will set
the Active status in the Status parameter. As soon as
the Unreported status is cleared by the alert reporting
task, another block alert may be reported without
clearing the Active status, if the subcode has changed.
22 ALARM_SUM None
The summary alarm is used for all process alarms in
the block. The cause of the alert is entered in the
subcode field. The first alert to become active will set
the Active status in the Status parameter. As soon as
the Unreported status is cleared by the alert reporting
task, another block alert may be reported without
clearing the Active status, if the subcode has changed.
23 ACK_OPTION None Used to set auto acknowledgment of alarms.
24 ALARM_HYS Percent
The amount the alarm value must return within the
alarm limit before the associated active alarm
condition clears.
25 HI_HI_PRI None The priority of the HI HI alarm.
26 HI_HI_LIM
EU of
PV_SCALE
The setting for the alarm limit used to detect the HI HI
alarm condition.
27 HI_PRI None The priority of the HI alarm.
28 HI_LIM
EU of
PV_SCALE
The setting for the alarm limit used to detect the HI
alarm condition.
29 LO_PRI None The priority of the LO alarm.
30 LO_LIM
EU of
PV_SCALE
The setting for the alarm limit used to detect the LO
alarm condition.
31 LO_LO_PRI None The priority of the LO LO alarm.
32 LO_LO_LIM
EU of
PV_SCALE
The setting for the alarm limit used to detect the LO
LO alarm condition.
33 HI_HI_ALM None
The HI HI alarm data, which includes a value of the
alarm, a timestamp of occurrence and the state of the
alarm.
34 HI_ALM None
The HI alarm data, which includes a value of the
alarm, a timestamp of occurrence and the state of the
alarm.
35 LO_ALM None
The LO alarm data, which includes a value of the
alarm, a timestamp of occurrence and the state of the
alarm.
36 LO_LO_ALM None
The LO LO alarm data, which includes a value of the
alarm, a timestamp of occurrence and the state of the
alarm.
Table D-1. Analog Input Function Block Parameters
Number Parameter Units Description