Quick Start Guide
13
December 2014
I5 FM Intrinsic Safety and Non-Incendive
Certificate: 3034378
Applicable Standards: Class 3600:1998, Class 3610:2010, Class 3810:2005,NEMA 250:
1997,ANSI/ISA-60079-0:2009, ANSI/ISA-60079-11:2009.
Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D.
Non-incendive for Class I, Division 2, Groups A, B, C, and D.
Intrinsically Safe Zone Marking: Zone 0, AEx ia llC
Temperature Codes T4 (T
amb
= -50 °C to 70 °C)
Intrinsically Safe and non-incendive when installed in accordance with Rosemount
drawing 00849-1000.
Enclosure Type 4X / IP66
Sensor Terminal Output Parameter Limits
Canadian Standards Association (CSA)
I6 CSA Intrinsic Safety
Certificate: 1261865
Applicable Standards: C22.2 25:1966, C22.2 30:1986, C22.2 94:1991, C22.2 142:1987,
C22.2 157:1992, C22.2 213:1987, CAN/CSA C22.2 0:2001, ANSI/ISA 12.27.01-2003,
C22.2 60529:2005
Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D.
Non-incendive for Class I, Division 2, Groups A, B, C, and D.
Temp Code T3C
Enclosure Type 4X / IP66
For use with Rosemount power module P/N 753-9220-0001 only.
Intrinsically Safe and non-incendive when installed in accordance with Rosemount
drawing 00849-1016.
Sensor Terminal Output Parameter Limits
U
o
= 6.6 Vdc
I
o
= 3.2 mA
P
o
= 5.1 mW
C
o
= 22 uF
L
o
= 1 H
U
o
= 6.6 Vdc
I
o
= 3.2 mA
P
o
= 20.4 mW
C
o
= 22 uF
L
o
= 1 H