Reference Manual
00809-0200-4420, Rev HB
Appendix D: Redundancy
January 2015
D.5 Diagnostics
The redundant system will perform many diagnostic checks to verify the health and
connectivity of the system.
Figure D-7. Redundancy Status (Diagnostics>Advanced>Redundancy Status)
These diagnostics can also be mapped to Modbus registers or OPC tags. The following table
covers what diagnostics are included on the Redundancy Status page as well as how they can be
mapped as parameters in Modbus or OPC.
Table D-1. Redundancy Diagnostics
Parameter Description Data type
REDUNDANT_HEALTHY
Overall redundancy status indicating the system is
ready for a switch-over
Boolean
RF_COVERAGE_FAILURE
Check to verify that both Gateways have the same
RF coverage of the wireless field network
Boolean
REDUNDANT_A_ONLINE Operational status of Gateway A Boolean
REDUNDANT_A_MASTER Indication if Gateway A is the active system Boolean
REDUNDANT_A_PING
Indication if Gateway A is able to ping designated
host IP address
Boolean
REDUNDANT_A_ETH0
Electrical connection status of the primary Ethernet
port for Gateway A
8-bit unsigned int
REDUNDANT_B_ONLINE Operational status of Gateway B Boolean
REDUNDANT_B_MASTER Indication if Gateway B is the active system Boolean
REDUNDANT_B_PING
Indication if Gateway B is able to ping designated
host IP address
Boolean
REDUNDANT_B_ETH0
Electrical connection status of the primary Ethernet
port for Gateway A
8-bit unsigned int