DeltaV Product Data Sheet
February 2015 – Page 8
Smart Wireless Gateway
1420 Gateway Product Certifications
Approved Manufacturing Locations
Rosemount Inc.—Chanhassen, Minnesota, USA.
Emerson Process Management GmbH & Co.—Karlstein,
Germany.
Emerson Process Management Asia Pacific Private
Limited—Singapore.
Beijing Rosemount Far East Instrument Co., Limited—
Beijing, China.
Telecommunication Compliance
All wireless devices require certification to ensure that they
adhere to regulations regarding the use of the RF
spectrum. Nearly every country requires this type of product
certification. Emerson is working with governmental
agencies around the world to supply fully compliant
products and remove the risk of violating country directives
or laws governing wireless device usage.
FCC and IC
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following conditions: This device
may not cause harmful interference. This device must
accept any interference received, including interference that
may cause undesired operation. This device must be
installed to ensure a minimum antenna separation distance
of 20 cm from all persons.
Ordinary Location Certification for FM
As standard, the Gateway has been examined and tested
to determine that the design meets basic electrical,
mechanical, and fire protection requirements by FM, a
nationally recognized testing laboratory (NRTL) as
accredited by the Federal Occupational Safety and Health
Administration (OSHA).
North American Certifications
(N5) FM Division 2, Non-incendive
Certificate Number: 3028321
Non-incendive for Class I, Division 2, Groups A, B, C,
and D
Dust Ignition-proof for Class II, III, Division 2, Groups E,
F, and G; Indoors/outdoor locations
Type 4X
Temperature Code: T4 (-40 °C < Ta < 60 °C)
Canadian Standards Association (CSA)
(N6) CSA Division 2, Non-incendive
Certificate Number: 1849337
Suitable for Class I, Division 2, Groups A, B, C, D
Dust Ignition-proof for Class II, Groups E, F, G
Suitable for Class III Hazardous Locations
Install per Rosemount drawing 01420-1011
Temperature Code: T4 (-40 °C < Ta < 60 °C)
CSA Enclosure Type 4X
European Union Directive Information
The EC declaration of conformity for all applicable
European directives for this product can be found on the
Rosemount website at www.rosemount.com. A hard copy
may be obtained by contacting your local sales
representative.
ATEX Directive (94/9/EC)
Emerson Process Management complies with the
ATEX Directive.
Electro Magnetic Compatibility (EMC) (2004/108/EC)
EN 61326-1: 2006
Radio and Telecommunications Terminal Equipment
Directive (R&TTE)(1999/5/EC)
Emerson Process Management complies with the
R&TTE Directive