8
Smart Wireless Gateway 1410
August 2014
Product Certifications
Approved Manufacturing Locations
Rosemount Inc. – Chanhassen, Minnesota, USA
Emerson Process Management Asia Pacific Private Limited -
Singapore
Telecommunication Compliance
All wireless devices require certification to ensure they adhere to
regulations regarding the use of the RF spectrum. Nearly every
country requires this type of product certification. Emerson is
working with governmental agencies around the world to
supply fully compliant products and remove the risk of violating
country directives or laws governing wireless device usage.
FCC and IC
This device complies with Part 15 of the FCC Rules. Operation is
subject to the following conditions: This device may not cause
harmful interference. This device must accept any interference
received, including interference that may cause undesired
operation. This device must be installed to ensure a minimum
antenna separation distance of 20 cm from all persons.
European Directive Information
The EC declaration of conformity can be found in the Quick Start
Guide (00825-0200-4410). The most recent revision can be
found at www.emersonprocess.com.
Ordinary Location Certification from FM
Approvals
As standard, the transmitter has been examined and tested to
determine that the design meets basic electrical, mechanical,
and fire protection requirements by FM Approvals, a nationally
recognized testing laboratory (NRTL) as accredited by the
Federal Occupational Safety and Health Administration (OSHA).
Hazardous Locations Certifications
North American Certifications
N5 FM Approvals, Nonincendive for Class I Division 2
Certificate No.: 3049590
Standards Used:Class 3600:2011, Class 3611:2004, Class
3810:2005
Markings: NI CL I, DIV. 2, GP A, B, C, D
Temperature code: T4 (-40 °C ≤ Ta ≤ 60 °C)
Special Condition of Use:
1. When installed as Division 2 equipment, the 1410 shall be
mounted within a tool-secured enclosure which meets the
requirements of ANSI/ISA 61010-1 and be capable of
accepting the applicable wiring methods per the NEC.
N6 CSA Class I Division 2
Certificate No.: 2646342
Standards Used: CSA Std. C22.2 No. 0-10, CSA Std. C22.2
No. 213 - M1987, CSA Std. C22.2 No.61010-1-12,
ANSI/ISA 12.12.01-2012, ANSI/ISA 61010-1-2012
Markings: SUITABLE FOR CL I, DIV. 2, GP A, B, C, D
Temperature code: T4 (-40 °C ≤ Ta ≤ 70 °C)
NM Technical Regulation Customs Union (EAC)
Contact an Emerson process management representative
for additional information.
Notes
- Shall be powered by a class 2 power supply.
- Suitable for dry indoor locations only.
- Equipment must be installed in a suitable tool accessible
enclosure subject to the end use application.